Input Signal(1)
4 to 20 mA dc, constant current with 30 Vdc maximum compliance voltage
Equivalent Circuit
The Type 646 equivalent circuit is a series circuit consisting of a constant voltage drop (battery) of approximately 2.1 Vdc and a total resistance of 143 ohms. Input is shunted by three 6.8 V zener diodes (see figure 2).
Output Signal(1)
0.2 to 1.0 bar (3 to 15 psig) direct acting only
Supply Pressure(1,4)
Recommended: 1.4 bar (20 psig)Minimum: 1.4 bar (20 psig)Maximum: 3.4 bar (50 psig)
Maximum Steady-State Air Consumption(1)(2)
Air consumption is proportional to output pressure. Maximum consumption at 1.0 bar (15 psig) output is 0.20 normal m3/hr (0.13 scfm).
Maximum Output Air Capacity(2)
8.0 normal m3/hr (5.0 scfm) at 1.4 bar (20 psig) supply pressure
Performance(3)
Reference Accuracy: ±0.5% of full scale output span; includes combined effects of hysteresis, linearity, and deadbandIndependent Linearity (1): ±0.5% of full scale output spanHysteresis (1): 0.4% of full scale output spanFrequency Response (1): Gain is attenuated 3 dB at 10 Hz with transducer output signal piped to a typical instrument inputTemperature Effect: ±4% of full scale output span per 100°F (55°C) changeSupply Pressure Effect: 0.2% of full scale output span per psi supply pressure changeVibration Effect: Less than 1% of full scale output span when tested to SAMA PMC 31.1, Condition 3 Electromagnetic Interference (EMI)(1): Tested per IEC 61326-1 (Edition 1.1). Conforms to the European EMC Directive. Meets emission limits for class A equipment (industrial locations) and class B equipment (domestic locations). Meets immunity requirements for industrial locations (Table A.1 in the IEC specification document). Immunity performance is shown in table 1.
Operating Ambient Temperature Limits(4)
-40 to 71°C (-40 to +160°F)
Housing
NEMA 3; IEC 529 IP54 weatherproof. Mount instrument with vent on side or bottom if weatherproofing is a concern.
Electrical Classification
Explosion proof, Dust-Ignition proof, DIV 2, Intrinsically Safe
Explosion proof, Non-incendive, Dust-Ignition proof, Intrinsically Safe
Intrinsically Safe and Type n Refer to the Hazardous Area Classification bulletins 9.2:001 series and 9.2:002 for additional information and/or approvals.
Construction Materials
Housing, Cap, and Relay Body: Die cast aluminum with less than 1% copper
Adjustments
Zero and Span: Trim potentiometers (20 turn) for zero and span adjustments are located under the housing cap
Connections
Supply and Output Pressure: 1/4-inch NPT female connectionVent: 1/4-inch NPT femaleElectrical: ■Standard 1/2-inch NPT or, ■Optional M20 or PG13 conduit adapter (see figure 4)Wire Size: 18 to 22 AWG
Mounting Position
Any position is acceptable for standard pipestand, panel, or actuator mounting. For weatherproof housing, mount the transducer to allow the vent to drain.
Approximate Weight (Transducer Only)
1.6 kg (3.5 pounds)
Options
Output pressure gauge
Close Section Above
Note: Fisher does not assume responsibility for the selection, use, or maintenance of any product. Responsibility for the selection, use, or maintenance of any Fisher product remains solely with the purchase and end-user.
To determine what ordering information is required, refer to the specification table. Carefully review the description of each specification. Specify the desired choice whenever there is a selection available. Also, specify options that are applicable to the application.