DVC6000 SIS Description
Close Section Above
Features
- Increased System Availability—The simple and secure method of partial stroke testing allows end-users to perform more frequent valve mechanical movement tests. This reduces the PFD factor. Because the test procedures are flexible, they can be conducted at any time, providing more assurance the system will be available upon demand. In addition, continuous valve monitoring through AMSTM ValveLink® Software provides awareness of the valve's status.
- Reduced Cost of Ownership—Lower base equipment cost with considerable reduction in testing time and a reduced manpower requirement makes this solution economically feasible. DVC6000 Series digital valve controllers in SIS solutions offer an economic alternative to expensive pneumatic test panels and skilled personnel presently required for testing Safety Instrumented System valves.
- Valuable Time Savings—Remote testing capability requires fewer maintenance inspection trips to the field thus saving considerable time. Using AMS ValveLink Software's Batch Runner to establish an automatic test routine can also provide increased time savings.
- Predictive Maintenance—DVC6000 Series instruments in SIS solutions permit using AMS ValveLink Software to provide Valve Degradation Analysis, which is important for critical valves in shut down systems. This may also reduce the amount of scheduled maintenance.
- Valve Stuck Alert—While performing the partial stroke test, if for any reason the valve is stuck, the digital valve controller will not completely exhaust the actuator pressure. This reduces the likelihood that the valve will slam shut should it become unstuck. The digital valve controller will abort the test and set an alert indicating that the valve is stuck. The alert is accessible through either the 375 Field Communicator or AMS ValveLink Software.
- System Audit Documentation—Using AMS ValveLink Software provides a time and date stamp on all tests and reports, which is important for documenting compliance with the requirements of statutory authorities.
- Verification—AMS ValveLink Software provides the capability for comparing and interpreting diagnostic data.
- Device Initiated Partial Stroke Test Available—DVC6000 Series digital valve controllers allow a partial stroke test, which ramps valve travel a small amount, while the valve is in-service and operating. Should a demand arise during the test, the test is overridden immediately and the valve moves to the safe state. The partial stroke test can be automatically scheduled and initiated by the device itself or can be performed manually by the user. Configuring the time interval between tests for a device initiated partial stroke test automates the process.
- Built-In Redundancy—When used in conjunction with a solenoid valve, as shown in figures 9 and 11, DVC6000 Series digital valve controllers in SIS solutions provide an inherent redundant pneumatic path. Should an emergency situation arise, the actuator pressure exhausts through either the solenoid valve or through the digital valve controller, allowing the valve to move to the safe position.
- Reduced Wiring Cost—DVC6000 Series instruments in SIS solutions eliminate the need for position transmitters and separate wiring from the transmitter. Through HART® protocol, the valve position is communicated over the same 4 to 20 mA analog loop that provides the valve control signal. A HART-to-analog signal converter in the control room can provide a 4 to 20 mA signal that is proportional to valve position. The HART-to-analog signal converter can also provide discrete contact outputs to the logic solver, which may replace hard-wired limit switches.
- Device Integrity Continuously Checked—When "End Point Pressure Control Mode" is enabled, the digital valve controller remains constantly in control while the valve is at its normal position (either fully open or fully closed); it is not allowed to reach a saturated state. The digital valve controller constantly tests its internal components, and if any component fault is detected, it sets an alert which may be accessed through either the 375 Field Communicator or AMS ValveLink Software.
- Manual Reset—The DVC6000 Series digital valve controller in SIS applications can be configured to hold the trip state until a local reset button is pressed. Manual reset can be initiated by pressing the built-in button on the optional LCP100 local control panel. Alternatively, if the LCP100 is not used, a user-supplied push button can be used to short the AUX terminals.
- Trigger Functionality—Data can be collected and stored in the microprocessor memory of the DVC6000 digital valve controller. Trip event data can be accessed for an audit and presented to a regulatory or insurance authority when the DVC6000 SIS operates with 4-20 mA. The trigger will initiate on-board data collection based on a change in actuator pressure, valve travel, input current, pressure differential, travel deviation, travel cutoff, or auxiliary input/external trigger. The data is stored on board the device for later retrieval, and is retained in the event of a power loss.
- Solenoid Testing—When a solenoid valve is installed between the DVC6000 pressure output and the actuator, the control valve assembly can be configured to verify the operation of the solenoid valve. In single acting actuator applications, the "unused" output port of the DVC6000 can be piped such that the pressure downstream of the solenoid valve is measured (see figure 2). When the solenoid valve is pulsed, the DVC6000 can sense the momentary pressure drop across the solenoid valve,
as shown in figure 3. If the pulse is short enough, the emergency shutdown valve will not move or disrupt the process. This not only increases the availability of the solenoid valve during a safety demand, but also enhances the reliability of the SIF (Safety Instrumented Function) loop.
- Spurious Trip Protection—The DVC6000 Series digital valve controller can be supplied with a reverse acting relay to provide maximum output pressure at minimum input signal. This solution provides trip protection because loss of control signal will not cause the valve to trip (i.e. the relay stays at maximum output pressure).
In point-to-point mode, (where the DVC6000 SIS is powered with 4 mA), the valve can be taken to its fail safe position by applying 20mA.
In multidrop mode, (where the DVC6000 SIS is powered with 24 VDC), a solenoid valve will be required to take the final control element to its fail safe position.
The DVC6000 digital valve controller also offers a diagnostic to test the operation of the solenoid valve when used with a single-acting actuator.
- Partial Stroke Testing—This test checks for valve movement. The partial stroke test can be initiated by an authorized technician with the 375 Field Communicator or AMS ValveLink Software. The technician may also initiate the test by shorting the AUX Terminal in the field with a push button located at the device, or remotely from the valve (figure 4) or by using an LCP100 local control panel (shown in figure 19). Initiating the test does not require removing any instrument covers or being near the valve during the test. Once initiated, the
automated test moves the valve to a predetermined value then returns the valve to its original position. The default value for valve movement is 10% from its original position, but can be custom set to any value up to 30% to meet plant safety guidelines.
The partial stroke test can reduce costly, labor intensive testing techniques. The simplicity of this automated test allows for more frequent online testing. More frequent testing enhances loop availability and increases the reliability of the system.
A partial stroke test can be initiated when the valve is operating at either 4 or 20 mA (point-to-point mode). In applications where a spurious trip is to be minimized, 4 mA is the normal operating position.
- Valve Signature—A valve signature obtained with AMS ValveLink Software can be used to easily determine valve packing problems (through friction data), leakage in the pneumatic pressurized path to the actuator (through the Pressure vs Travel graph), valve sticking, actuator spring rate, and bench set.
Any time a partial stroke test is run on the valve, a partial stroke valve signature and analysis, shown in figure 5, is available. Comparing valve signature results can be used to determine if valve response has degraded over time.
In addition, when the valve is not online, several full stroke valve diagnostic tests can be run, including valve signature, dynamic error band, and step response. AMS ValveLink Software enables simultaneous multiple overlay of up to ten tests (partial stroke test or dynamic scan or a combination of both tests) and allows end-user capability to trend valve history. Pressure and travel vs. time plot provides the exact status of the valve movement, helping to critically analyze events like a "Safety Demand". These tests can also be used to evaluate valve performance, such as stroking time and shutoff capability. Running these tests when the valve is first installed in the safety system allows establishing a bench mark for valve performance. The results of these tests can be compared to results from later tests to determine if valve performance has degraded.
- Automatic Testing—The AMS ValveLink Software Batch Runner tool can be used to automate diagnostic testing. It provides the capability of running multiple tasks back to back on multiple valves with no intervention. This permits the user to do other things while Batch Runner does the work.
- Travel Record—The cycle counter and travel accumulator provide a record of the number of cycles and percentage of travel accumulated over time.
- Alerts—All device alerts are available through either the 375 Field Communicator or AMS ValveLink Software. Alerts are immediately available, and logged if AMS ValveLink Software is set up for alert scanning. Alerts are also stored in an alert record in the instrument. Alerts in the alert record can be retrieved by connecting a Field Communicator or AMS ValveLink Software to the device. Each alert is recorded with a time and date stamp to allow the operator to determine the nature of the alert and when it occurred.
- Alert Notification—AMS ValveLink Software Event Messenger allows notifying key people of critical alerts via e-mail. AMS ValveLink Software can be set up to automatically send an e-mail when a specified alert occurs on a final control element in a Safety Instrumented System (figure 6). This e-mail could also be setup to send a text message. The capability can be setup to notify a designated technician if a specific alert, or sets of alerts, occurred on a predefined set of safety shutdown valves. This means key plant operation personnel can be continuously informed of alert status, no matter where they are, enabling them to provide more timely and precise corrective action.
- Adjustable Travel Cutoff—Travel Cutoffs are adjustable when the DVC6000 SIS is operating with a 4-20 mA current. The Setup Wizard automatically sets travel cutoffs at 50%, making the DVC6000 SIS work like an on-off device. At current levels from 4.0 to 11.99 mA, the DVC6000 SIS will provide minimum output pressure, and at 12 to 20 mA, the DVC6000 SIS will provide full output pressure.
A user can customize valve response to the control signal by changing the travel cutoffs. For example, it is possible to have the valve throttle between 10 and 90% open, but work as an on-off valve between 0% to 10% and 90% to 100% opening. The user now has a standard throttling control valve between 10% and 90% opening, but has an SIS outside of this range. While in SIS mode, in this example, partial stroke and pressure control mode can be enabled during travel greater than 90%.
- Travel Characterization—The DVC6000 SIS provides flexibility to configure quick open, linear, equal percentage, or custom characterization.
- Signature Analyzer—An additional diagnostic is available through AMS ValveLink Software for the possible indication of a broken shaft or stem, as shown in figure 7. Stick-Slip, a new diagnostic also available through AMS ValveLink Software (see figure 8), is used to indicate inherent dead motion and degraded performance.
- Enhanced Tuning Capabilities—Large size valves and actuators are often equipped with air accessories to improve stroking speed requirements. DVC6000 SIS firmware has simple parameter choices to allow the operator to more easily tune valves with accessories.
Close Section Above
Installing DVC6000 Series Instruments in SIS Systems
- 2-wire system
- 4-wire system
Installations with the digital valve controller in 2-wire systems (multidrop mode) are shown in figures 9 and 10. In installations that include a solenoid valve with the digital valve controller, the logic solver provides a single 24 volt DC source to provide power for both the solenoid valve and the digital valve controller. Installations with the digital valve controller in a 4-wire system (point-to-point mode) are shown in figure 11. These installations require two separate sources: a 24 volt DC source (from the Logic Solver) for the solenoid valve and a 4 to 20 milliamp DC current source (either from the Logic Solver or the DCS control system) for the digital valve controller.
In installations that include a solenoid valve, a redundant pneumatic path exists, i.e., the actuator pressure will always be able to exhaust to allow the valve to move to the safe position. If the solenoid valve fails, the actuator pressure will exhaust through the digital valve controller. If the digital valve controller fails, the actuator pressure will exhaust through the solenoid valve. If necessary, the solenoid valve can have larger ports to allow the safety shutdown valve to meet any response time criteria.
2-wire system installations:
- Reduce wiring cost for new installations or no additional wiring cost for existing installations
- Save an I/O card in the control room
- Require a line conditioner that adds an approximate 2 volt DC line drop (in installations that include a solenoid valve) or can use a HART-pass through multiplexer, which has the built in capability to allow HART communication without a line conditioner.
- Require a low power solenoid valve (if the installation includes a solenoid valve)
4-wire system installations:
- Permit the digital valve controller to continue to communicate even during emergency conditions (on demand). This allows the digital valve controller to provide valuable trending information through AMS ValveLink Software. Being able to record the valve action can provide important evidence that the valve did stroke upon demand.
- Require an additional pair of wires
- Permit the use of existing solenoid valves which may be powered with 48 volts DC, 120 volts AC, etc.
Close Section Above
Valve and Actuator Selection
Close Section Above
TÜV Certification
Close Section Above
DVC6000 Installation
Close Section Above
Type LCP100 Local Control Panel
Close Section Above
Ordering Information
Refer to the Specifications section. Carefully review each specification and indicate your choice whenever a selection is to be made.
When ordering, specify:
1. Digital valve controller type number
2. DVC6000 power [24 VDC (multi-drop) or 4-20 mA current loop (point-to-point)]
3. Valve style (sliding-stem or rotary)
4. Actuator (spring and diaphragm or piston with spring return)
5. Actuator manufacturer (Fisher or other)
6. Actuator type and size
7. Positioner Action (pneumatic relay) - Direct / Reverse
8. Valve failure action (fail close or fail open)
9. Mechanical position indicator, if required
10. LCP100 local control panel, if required
Close Section Above
DVC6000 Specifications
Available Configurations
Valve-Mounted Instrument: DVC6010: Sliding-stem applications DVC6020: Rotary applications and long-stroke sliding-stem applications DVC6030: Quarter-turn rotary applications
All units can be used in either 4-wire or 2-wire system installations.
DVC6000 Series digital valve controllers must have the Safety Instrumented System Application (SIS) option
Remote-Mounted Instrument (1): DVC6005: Base unit for 2-inch pipestand or wall mounting DVC6015: Feedback unit for sliding-stem applications DVC6025: Feedback unit for rotary or long-stroke sliding-stem applications DVC6035: Feedback unit for quarter-turn rotary applications
DVC6000 Series digital valve controllers can be mounted on Fisher and other manufacturers rotary and sliding-stem actuators.
Input Signal
Point-to-Point:. Analog Input Signal: 4-20 mA DC, nominal; split ranging available Minimum Voltage Available at Instrument Terminals must be 10.5 volts DC for analog control, 11 volts DC for HART communication (see instrument instruction manual for details) Minimum Control Current: 4.0 mA Minimum Current w/o Microprocessor Restart: 3.5 mA Maximum Voltage: 30 volts DC Overcurrent Protection: Input circuitry limits current to prevent internal damage Reverse Polarity Protection: No damage occurs from reversal of loop current
Multi-drop:. Instrument Power: 11 to 30 volts DC at approximately 8 mA Reverse Polarity Protection: No damage occurs from reversal of loop current
Output Signal
Pneumatic signal as required by the actuator, up to 95% of supply pressure Minimum Span: 0.4 bar (6 psig) Maximum Span: 9.5 bar (140 psig) Action: ■Double, ■Single Direct, and ■Single Reverse
Supply Pressure(2)
Minimum Recommended: 0.3 bar (5 psig) higher than maximum actuator requirements Maximum: 10.0 bar (145 psig) or maximum pressure rating of the actuator, whichever is lower
Steady-State Air Consumption(3,4)
Low Bleed Relay: At 1.4 bar (20 psig) supply pressure: Average value 0.056 normal m3/hr (2.1 scfh) At 5.5 bar (80 psig) supply pressure: Average value 0.184 normal m3/hr (6.9 scfh)
The low bleed relay is the standard relay for DVC6000 SIS tier, used for On/Off applications. Performance may be affected in throttling applications.
Standard Relay: At 1.4 bar (20 psig) supply pressure: Less than 0.38 normal m3/hr (14 scfh) At 5.5 bar (80 psig) supply pressure: Less than 1.3 normal m3/hr (49 scfh)
Maximum Output Capacity(3,4)
At 1.4 bar (20 psig) supply pressure: 10.0 normal m3/hr (375 scfh) At 5.5 bar (80 psig) supply pressure: 29.5 normal m3/hr (1100 scfh)
Independent Linearity(5)
±0.50% of output span
Electromagnetic Interference (EMI)
Tested per IEC 61326-1 (Edition 1.1). Complies with European EMC Directive. Meets emission levels for Class A equipment (industrial locations) and Class B equipment (domestic locations). Meets immunity requirements for industrial locations (Table A.1 in the IEC specification document). Immunity performance is shown in table 1.
IEC 61010 Compliance Requirements (Valve-Mounted Instruments Only)
Power Source: The loop current must be derived from a separated extra-low voltage (SELV) power source Environmental Conditions: Installation Category I
Electrical Classification
Hazardous Area:

Explosion proof, Division 2, Dust-Ignition proof, Intrinsic Safe

Explosion proof, Non-incendive, Dust-Ignition proof, Intrinsic Safety

Flameproof, Type n, Intrinsic Safety

Flameproof, Type n, Intrinsic Safety

Flameproof, Intrinsic Safety

Flameproof, Intrinsic Safety
Refer to tables 2, 3, 4, 5, 6, and 7 for specific approval information
Electrical Housing: Meets NEMA 4X, CSA Type 4X, IEC 60529 IP66
Auxiliary Terminal Contact: Nominal Electrical Rating 3V, <1 mA; It is recommended that the switch be sealed or have gold plated contacts to avoid corrosion.
Other Classifications/Certifications

Japan

Korea Industrial Safety Corp.

Russian GOST-R

Russian - Federal Service of Technological, Ecological and Nuclear Inspectorate
Contact your Emerson Process Management sales office for classification/certification specific information
Connections
Supply Pressure: 1/4 NPT internal and integral pad for mounting 67CFR regulator Output Pressure: 1/4 NPT internal Tubing: 3/8-inch metal, recommended Vent (pipe-away): 3/8 NPT internal Electrical: 1/2 NPT internal conduit connection. optional—M20 internal conduit connection, spring clamp terminal connection(6) Operating Ambient Temperature Limits(2)
-40 to 80°C (-40 to 176°F) for most approved valve-mounted instruments -40 to 125°C (-40 to 257°F) for remote-mounted feedback unit. -52 to 80°C (-62 to 176°F) for valve-mounted instruments utilizing the Extreme Temperature option (fluorosilicone elastomers).
Construction Materials
Housing, module base and terminal box: ASTM B85 A03600 low copper aluminum alloy (standard)
CF8M (cast 316 stainless steel) (optional for valve-mounted instruments only) Cover: Thermoplastic polyester Elastomers Standard: Nitrile Optional: Fluorosilicone
Stem Travel
DVC6010, DVC6015: 0 to 102 mm (4 inches) maximum travel span 0 to 9.5 mm (0.25 inches) minimum travel span
DVC6020, DVC6025: 0 to 606 mm (23.875 inches) maximum travel span
Shaft Rotation (DVC6020, DVC6025, DVC6030 and DVC6035)
0 to 50 degrees minimum 0 to 90 degrees maximum
Mounting
Designed for direct actuator mounting or remote pipestand or wall mounting. Mounting the instrument vertically, with the vent at the bottom of the assembly, or horizontally, with the vent pointing down, is recommended to allow drainage of moisture that may be introduced via the instrument air supply.
Weight
Valve-Mounted Instruments. Aluminum: 3.5 kg (7.7 lbs) Stainless steel: 7.7 kg (17 lbs)
Remote-Mounted Instruments. DVC6005 Base Unit: 4.1 kg (9 lbs) DVC6015 Feedback Unit: 1.3 kg (2.9 lbs) DVC6025 Feedback Unit: 1.4 kg (3.1 lbs) DVC6035 Feedback Unit: 0.9 kg (2.0 lbs)
Options
■Supply and output pressure gauges or ■Tire valves, ■Integral mounted filter regulator, ■Stainless steel housing, module base and terminal box (valve-mounted instruments only), ■Standard Relay, ■Extreme Temperature, ■Beacon Indicator, ■LCP100 local control panel
Close Section Above
Additional System Components: Specifications, Requirements, and Functionality
Type LC340 SIS Line Conditioner, figure 21. (Required for 2-wire system installations with solenoid valve)
Input Current(1): equal to load requirements, not to exceed 100 mA Input Voltage(1): load voltage + (30 ohms x load current); nominally 24 volts DC. See figure 20.
Ambient Operating Temperature(3): -40 to 85°C (-40 to 185°F) Ambient Relative Humidity: 5-95% Electrical Classification: Per IEC 61326-1 Complies with test requirements for I/O Signal/Control ports on equipment intended for use in industrial environments Mounting: standard 35 mm DIN rail Installation Environment: Marshalling cabinet, I/O cabinet, or junction box Dimensions: 75 mm (3 inches) long by 12.5 mm (0.5 inches) wide by 60 mm (2.4 inches) deep
Solenoid Valve
ASCO® Model EF8316G303, EF8316G304, or equivalent low power solenoid valve for a 2-wire system. ASCO Model EF8316G3, EF8316G4, or equivalent solenoid valve for a 4-wire system. Body Size: 3/8 or 1/2-inch Orifice Size: 5/8-inch Operating Voltage: 24 volt DC Body Material: brass Body and orifice selection may vary with actuator type and size, type of media, etc. Solenoid model number will change if size and body material or electrical ratings change.
Type LCP100 Local Control Panel
Power Options (switch selectable) ■ External—Maximum Continuous Current: 24 VDC +/- 10% @ 50 mA maximum; Maximum Inrush: 100 mA or ■ Loop: 8-20 mA Temperature Limits(3): -40 to 80°C (-40 to 176°F) for most approved valve-mounted instruments Maximum distance between LCP100 and DVC6000 digital valve controller: Cable length is limited by maximum cable capacitance of 18000 pF. Typical 56 meters (185 feet) with 18 AWG shielded Audio, Control and Instrumentation Cable
Type LCP100 Local Control Panel (continued)
Electrical Classification

Ex em[ib] IIC T5 for Class 1 Zone 1 (pending agency approval)(2) 
Ex em[ib] IIC T5 for Class 1 Zone 1 (pending agency approval)(2)
Enclosure Rating: Agency approval pending(2)
Close Section Above
Additional System Components: Specifications, Requirements, and Functionality
Electromagnetic Interference (EMI): Tested per IEC 61326-1 (Edition 1.1). Complies with European EMC Directive. Meets emission limits for class A equipment (industrial locations) and class B equipment (domestic locations). Meets immunity requirements for industrial locations (Table A.1 in the IEC specification document).
Connections: Conduit— ■ 3/4 NPT or ■ M20 Wiring: 14 to 26 AWG Electrical Installation: Wires are polarity sensitive Compatibility: Requires DVC6000 SIS with Firmware revision 7 or later Installation Orientation: Wiring entrance must be pointed down for self-draining Push buttons: Protected with lockable covers Dimensions: 253.1 mm (10 inches) long by 109.5 mm (4.3 inches) wide by 127.8 mm (5 inches) deep. See figure 22. Approximate Weight: 2.2 kg (4.9 lbs)
Lights Green: Solid when the valve is at its normal operating position, and loop current is normal. Flashing when the valve is not at its normal operating position, and loop current is normal.
Red: Solid when the valve is at its Fail Safe State and loop current is tripped. Flashing when valve is not at its Fail Safe State and loop current is tripped.
Amber (Ready-to-Reset): Solid when the valve is latched in the trip position, and loop current is normal.
Type LCP100 Local Control Panel (continued)
Buttons Green: •After an emergency demand— commands the valve to its normal position only after control current is restored (manual reset). •During a test— abort test
Red: Always commands the valve to its Fail Safe State regardless of the control current.
Black: Press and hold for 3 to 10 seconds. Commands the configured partial stroke test. Can be overridden by the Close button, Open button, or Emergency Demand. •During a test— abort test
Close Section Above
Related Documents
These documents are available from your Emerson Process Management sales office. Also visit our website at www.FIELDVUE.com.
- TÜV Certificate Nr./No. 968/EZ 127.00/02
- TÜV Report for DVC6000 SIS—No. 968/EZ 127.00/02
- FMEDA Report for DVC6000 SIS- Form 5742
- FMEDA Report for LC340 Line Conditioner - Form 5749
- FIELDVUE® DVC6000 Series Digital Valve Controllers for Safety Instrumented System (SIS) Solutions - Form 5807
Note
Neither Emerson, Emerson Process Management, nor any of their affiliated entities assumes responsibility for the selection, use, and maintenance of any product. Responsibility for the selection, use, and maintenance of any product remains with the purchaser and end-user.
Close Section Above
Table
Table 1. DVC6000 Series Digital Valve Controllers—Immunity Performance
| Port |
Phenomenon |
Basic Standard |
Test Level |
Performance Criteria(1) |
Point-to-Point Mode |
Multi-drop Mode |
| Enclosure |
Electrostatic discharge (ESD) |
IEC 61000-4-2 |
4 kV contact 8 kV air |
A(2) |
A |
| Radiated EM field |
IEC 61000-4-3 |
80 to 1000 MHz @ 10V/m with 1 kHz AM at 80% |
A |
A |
| Rated power frequency magnetic field |
IEC 61000-4-8 |
60 A/m at 50 Hz |
A |
A |
| I/O signal/control |
Burst |
IEC 61000-4-4 |
1 kV |
A(2) |
A |
| Surge |
IEC 61000-4-5 |
1 kV (line to ground only, each) |
A(2) |
A |
| Conducted RF |
IEC 61000-4-6 |
150 kHz to 80 MHz at 3 Vrms |
A |
A |
|
Close Section Above
Table 2. DVC6000 Series, Hazardous Area Classifications for Canada—CSA
| CERTIFICATION BODY |
TYPE |
CERTIFICATION OBTAINED |
ENTITY RATING |
TEMPERATURE CODE |
ENCLOSURE RATING |
| CSA |
DVC60x0 DVC60x0S (x = 1,2,3) |
(Intrinsic Safety) Class/Division Class I,II,III Division 1 GP A,B,C,D, E,F,G per drawing 29B3428 |
Vmax = 30 VDC Imax = 226 mA Ci = 5 nF Li = 0.55 mH |
T5(Tamb ≤ 80°C) |
4X |
(Explosion Proof) Class/Division Class I, Division 1 GP B,C,D |
- - - |
T6(Tamb ≤ 80°C) |
4X |
Class I Division 2 GP A,B,C,D Class II Division 1 GP E,F,G Class III Division 1 |
- - - |
T6(Tamb ≤ 80°C) |
4X |
| DVC6005 |
(Intrinsic Safety) Class/Division Class I,II,III Division 1 GP A,B,C,D,E, F,G per drawing 29B3520 |
Vmax = 30 VDC Imax = 226 mA Ci = 5 nF Li = 0.55 mH |
Voc = 9.6 VDC Isc = 3.5 mA Ca = 3.6 μF La = 100 mH |
T6(Tamb ≤ 60°C) |
4X |
(Explosion Proof) Class/Division Class I, Division 1 GP C,D |
- - - |
T6(Tamb ≤ 60°C) |
4X |
Class I Division 2 GP A,B,C,D Class II Division 1 GP E,F,G Class III Division 1 |
- - - |
T6(Tamb ≤ 60°C) |
4X |
DVC60x5 (x = 1,2,3) |
(Intrinsic Safety) Class/Division Class I,II,III Division 1 GP A,B,C,D, E,F,G per drawing 29B3520 |
Vmax = 10 VDC Imax = 4 mA Ci = 0 nF Li = 0 mH |
T4(Tamb ≤ 125°C) T5(Tamb ≤ 95°C) T6(Tamb ≤ 80°C) |
4X |
(Explosion Proof) Class/Division Class I, Division 1 GP B,C,D |
- - - |
T4(Tamb ≤ 125°C) T5(Tamb ≤ 95°C) T6(Tamb ≤ 80°C) |
4X |
Class I Division 2 GP A,B,C,D Class II Division 1 GP E,F,G Class III Division 1 |
- - - |
T4(Tamb ≤ 125°C) T5(Tamb ≤ 95°C) T6(Tamb ≤ 80°C) |
4X |
Close Section Above
Table 3. DVC6000 Series, Hazardous Area Classifications for United States—FM
| CERTIFICATION BODY |
TYPE |
CERTIFICATION OBTAINED |
ENTITY RATING |
TEMPERATURE CODE |
ENCLOSURE RATING |
| FM |
DVC60x0 DVC60x0S (x = 1,2,3) |
(Intrinsic Safety) Class/Division Class I,II,III Division 1 GP A,B,C,D,E, F,G per drawing 29B3427 |
Vmax = 30 VDC Imax = 226 mA Ci = 5 nF Li = 0.55 mH Pi = 1.4 W |
T5(Tamb ≤ 80°C) |
4X |
(Explosion Proof) Class/Division Class I, Division 1 GP B,C,D |
- - - |
T6(Tamb ≤ 80°C) |
4X |
Class I Division 2 GP A,B,C,D Class II,III Division 1 GP E,F,G Class II,III Division 2 GP F,G |
- - - |
T6(Tamb ≤ 80°C) |
4X |
| DVC6005 |
(Intrinsic Safety) Class/Division Class I,II,III Division 1 GP A,B,C,D, E,F,G per drawing 29B3521 |
Vmax = 30 VDC Imax = 226 mA Ci = 5 nF Li = 0.55 mH Pi = 1.4 W |
Voc = 9.6 VDC Isc = 3.5 mA Ca = 3.6 μF La = 100 mH Po = 8.4 mW |
T6(Tamb ≤ 60°C) |
4X |
(Explosion Proof) Class/Division Class I, Division 1 GP C,D |
- - - |
T6(Tamb ≤ 60°C) |
4X |
Class I Division 2 GP A,B,C,D Class II,III Division 1 GP E,F,G Class II,III Division 2 GP F,G |
- - - |
T6(Tamb ≤ 60°C) |
4X |
DVC60x5 (x = 1,2,3) |
(Intrinsic Safety) Class/Division Class I,II,III Division 1 GP A,B,C,D, E,F,G per drawing 29B3521 |
Vmax = 10 VDC Imax = 4 mA Ci = 0 nF Li = 0 mH Pi = 10 mW |
T4(Tamb ≤ 125°C) T5(Tamb ≤ 95°C) T6(Tamb ≤ 80°C) |
4X |
(Explosion Proof) Class/Division Class I, Division 1 GP A,B,C,D |
- - - |
T4(Tamb ≤ 125°C) T5(Tamb ≤ 95°C) T6(Tamb ≤ 80°C) |
4X |
Class I Division 2 GP A,B,C,D Class II,III Division 1 GP E,F,G Class II,III Division 2 GP F,G |
- - - |
T4(Tamb ≤ 125°C) T5(Tamb ≤ 95°C) T6(Tamb ≤ 80°C) |
4X |
Close Section Above
Table 4. DVC6000 Series, Hazardous Area Classifications—ATEX
| CERTIFICATE |
TYPE |
CERTIFICATION OBTAINED |
ENTITY RATING |
TEMPERATURE CODE |
ENCLOSURE RATING |
| ATEX |
DVC60x0 DVC60x0S (x = 1,2,3) |
II 1 G D Gas EEx ia IIC T5/T6—Intrinsic Safety Dust T85°C (Tamb ≤ 80°C) |
Ui = 30 VDC Ii = 226 mA Ci = 5 nF Li = 0.55 mH Pi = 1.4 W |
T5(Tamb ≤ 80°C) T6 (Tamb ≤75°C) |
IP66 |
II 2 G D Gas EEx d IIB+H2 T5/T6—Flameproof Dust T90°C (Tamb ≤ 85°C) |
- - - |
T5(Tamb ≤ 85°C) T6 (Tamb ≤ 75°C) |
IP66 |
II 3 G D Gas EEx nCL IIC T5/T6—Type n Dust T85°C (Tamb ≤ 80°C) |
- - - |
T5(Tamb ≤ 80°C) T6 (Tamb ≤ 75°C) |
IP66 |
| DVC6005 |
II 1 G D Gas EEx ia IIC T5/T6—Intrinsic Safety Dust T85°C (Tamb ≤ 80°C) |
Ui = 30 VDC Ii = 226 mA Ci = 5 nF Li = 0.55 mH Pi = 1.4 mW |
Uo = 9.6 VDC Io = 3.5 mA Co = 3.6 uF Lo = 100 mH Po = 8.4 mW |
T5(Tamb ≤ 80°C) T6(Tamb ≤ 75°C) |
IP66 |
II 2 G D Gas EEx d IIB T5/T6—Flameproof Dust T90°C (Tamb ≤ 80°C) |
- - - |
T5(Tamb ≤ 80°C) T6 (Tamb ≤ 70°C) |
IP66 |
II 3 G D Gas EEx nL IIC T5/T6—Type n Dust T85°C (Tamb ≤ 80°C) |
- - - |
T5(Tamb ≤ 80°C) T6 (Tamb ≤ 75°C) |
IP66 |
DVC60x5 (x = 1,2,3) |
II 1 G D Gas EEx ia IIC T4/T5/T6—Intrinsic Safety Dust T130°C (Tamb ≤ 125°C) |
Ui = 10 VDC Ii = 4 mA Ci = 0 nF Li = 0 mH Pi = 10 mW |
T4(Tamb ≤ 125°C) T5(Tamb ≤ 95°C) T6(Tamb ≤ 80°C) |
IP66 |
II 2 G D Gas EEx d IIC T4/T5/T6—Flameproof Dust T130°C (Tamb ≤ 125°C) |
- - - |
T4(Tamb ≤ 125°C) T5(Tamb ≤ 95°C) T6(Tamb ≤ 80°C) |
IP66 |
II 3 G D Gas EEx nA IIC T4/T5/T6—Type n Dust T130°C (Tamb ≤ 125°C) |
- - - |
T4(Tamb ≤ 125°C) T5(Tamb ≤ 95°C) T6(Tamb ≤ 80°C) |
IP66 |
Close Section Above
Table 5. DVC6000 Series, Hazardous Area Classifications—IECEx
| CERTIFICATE |
TYPE |
CERTIFICATION OBTAINED |
ENTITY RATING |
TEMPERATURE CODE |
ENCLOSURE RATING |
| IECEx |
DVC60x0 DVC60x0S (x = 1,2,3) |
Gas Ex ia IIC T5/T6—Intrinsic Safety |
Ui = 30 VDC Ii = 226 mA Ci = 5 nF Li = 0.55 mH Pi = 1.4 W |
T5(Tamb ≤ 80°C) T6 (Tamb ≤ 75°C) |
IP66 |
Gas Ex d IIB+H2 T5/T6—Flameproof |
- - - |
T5(Tamb ≤ 80°C) T6 (Tamb ≤ 75°C) |
IP66 |
Gas Ex nC IIC T5/T6—Type n |
- - - |
T5(Tamb ≤ 80°C) T6 (Tamb ≤ 75°C) |
IP66 |
| DVC6005 |
Gas Ex ia IIC T5/T6—Intrinsic Safety |
Ui = 30 VDC Ii = 226 mA Ci = 5 nF Li = 0.55 mH Pi = 1.4 W |
Uo = 9.6 VDC Io = 3.5 mA Co = 3.6 μF Lo = 100 mH Po = 8.4 mW |
T5(Tamb ≤ 80°C) T6 (Tamb ≤ 75°C) |
IP66 |
Gas Ex d IIB T5/T6—Flameproof |
- - - |
T5(Tamb ≤ 80°C) T6 (Tamb ≤ 75°C) |
IP66 |
Gas Ex nC IIC T5/T6—Type n |
- - - |
T5(Tamb ≤ 80°C) T6 (Tamb ≤ 75°C) |
IP66 |
DVC60x5 (x = 1,2,3) |
Gas Ex ia IIC T4/T5/T6—Intrinsic Safety |
Ui = 10 VDC Ii = 4 mA Ci = 0 nF Li = 0 mH Pi = 10 mW |
T4(Tamb ≤ 125°C) T5(Tamb ≤ 95°C) T6(Tamb ≤ 80°C) |
IP66 |
Gas Ex d IIC T4/T5/T6—Flameproof |
- - - |
T4(Tamb ≤ 125°C) T5(Tamb ≤ 95°C) T6(Tamb ≤ 80°C) |
IP66 |
Gas Ex nA IIC T4/T5/T6—Type n |
- - - |
T4(Tamb ≤ 125°C) T5(Tamb ≤ 95°C) T6(Tamb ≤ 80°C) |
IP66 |
Close Section Above
Table 6. DVC6000 Series, Hazardous Area Classifications—NEPSI
| CERTIFICATE |
TYPE |
CERTIFICATION OBTAINED |
ENTITY RATING |
TEMPERATURE CODE |
ENCLOSURE RATING |
| NEPSI |
DVC60x0 (x =1,2,3) |
Gas Ex ia IIC T5/T6 —Intrinsic Safety Dust DIP A21 T5 |
Ui = 30 V Ii = 226 mA Ci = 5 nF Li = 0.55 mH Pi = 1.4 W |
T5(Tamb ≤ 80°C) T6 (Tamb ≤ 75°C) |
IP66 |
Gas Ex d IIC T5/T6(1) —Flameproof Dust DIP A21 T5 |
- - - |
T5(Tamb ≤ 80°C) T6 (Tamb ≤ 75°C) |
IP66 |
|
|
Close Section Above
Table 7. DVC6000 Series, Hazardous Area Classifications—INMETRO
| CERTIFICATE |
CERTIFICATION OBTAINED |
ENTITY RATING |
TEMPERATURE CODE |
ENCLOSURE RATING |
| INMETRO |
BR-Ex ia IIC T5 |
Ui = 30 V Ii = 180 mA Ci = 5 nF Li = 0.55 mH Pi = 1.4 W |
T5(Tamb ≤ 80°C) |
|
| BR-Ex d IIB+H2 T6 |
- - - |
T6 (Tamb ≤ 75°C) |
|
Close Section Above
Close Section Above
|